Available PLC
*
When using RS-232C cable made by IDEC [FC2A-KC2] or [FC2A-KC4C], connect the cable of
[Wiring Diagram 1] to the D-dub 9 pins side of [FC2A-KC2] or [FC2A-KC4C] to communicate with POD .
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
Available Memory
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
MICRO3
RS-232C Cable made by IDEC [FC2A-KC1]
or
* Cable made by IDEC [FC2A-KC2]
+RS-232C [Wiring Diagram 1]
PLC
Wiring Diagram
Selet PLC Type
MICRO3
MICRO Smart
RS-232C * Cable made by IDEC [FC2A-KC4C]
+RS-232C [Wiring Diagram 1]
MICRO Smart
9600bps
1
Even
Even
1
Port
Baud Rate
Parity
Data Length
Stop Bit
Item Setting of PLC
9600bps
77
11
Transmission
Code
Comm. Parameter of POD
IDEC PLC
46
Memory TYPE Remarks
D(data register) 0
I (input relay) 1
Q(output relay) 2
M(internal relay) 3
R (shift register) 4
TS (timer/set value) 5
TN (timer/elapsed value) 6
T (timer/contact) 7 Read only
CS (timer/set value) 8
CN (counter/elapsed value) 9
C(counter/contact) 10 Read only
46 IDEC PLC