Available Memory
MOELLER PLC
Communication Setting
The recommended communication parameter setting of both PLC and V6 is as follows:
Available PLC
51
51 MOELLER PLC
9600bps 9600bps
None
8
Baud Rate
Parity
Transmission
code
Data Length
Stop Bit
1
8
1
Item Setting of PLC
Port 1 1
Comm. Parameter of POD
None
PS4-201-MM1(PRG port)
PS4
PLC
Select PLC Type
Wiring Diagram
RS-232C [Wiring Diagram 1]
+
ZB4-303-KB1 Cable made by MOELLER
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
Wiring
The following is a diagram to show the wiring of the cable which connects POD to PLC.
RS-232C
Wiring Diagram 1
FG
RD
SD
SG
1
3
2
7
TX
RX
SG
POD (CN1)
D-sub 25pin(Male: )
PLC
* Use twist shielded cables.
3
2
5
D-sub 9pin(Male: )
Memory TYPE Remarks
M(Marker) 0 MW as word device