VIGOR PLC
Available PLC
54
Communication Setting
The recommended communication parameter setting of both PLC and POD is as follows:
M series
PLC Link Unit
Wiring Diagram
RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 2]
COM PORT
Select PLC Type
M1-CPU1
Port 0
19200bps
Even
7
Baud Rate
Parity
Transmission
Code
Data Length
Stop Bit
1
Item Setting of PLC
0
19200bps
Even
7
1
Comm. Parameter of POD
Available Memory
*1 In case of the items which can display double word data (e.g. data display, graph, sampling), the
data is managed as double word data.
Both bit data and word data are managed as lower-half 16 bits data.
Input : 16 upper-half bits are ignored.
Output : “0” is written in the 16 upper-half bits.
Set the memory to the extent of the memory range of each PLC model.
Use TYPE number to assign indirect memory for macro programs.
Memory TYPE Remarks
D (data register/special register) 0
X (input relay) 1
Y(output relay) 2
M (internal relay/special relay) 3
S(internal relay/step relay) 4
T (timer/current value) 5
C(counter/current value) 6
32C (high-speed counter/current value) 7 *1
TS (timer/contact) 8
CS (counter/contact) 9
TC (timer/coil) 10
CC (counter/coil) 11